FEATURES:
True RMS measurements
Harmonic distortion display ( 31 harmonics)
Oscilloscope, waveform display
Max demand display
User configurable display screen
Fully isolated RS-485 serial port
MODBUS-RTU communication
2 configurable relay outputs
Energy pulse output capability
Optically isolated, configurable digital inputs
Switched dual active-reactive power counters
Independent mains/generator energy metering
Configurable user counters
Voltage transformer ratio for MV applications
Password protected front panel programming
High visibility, 128x64 pixels graphic LCD
Reduced panel depth
Wide operating temperature range
Sealed front panel (IP54)
Plug-in connection system
TECHNICAL SPECIFICATIONS:
Power Supply Input:
170 - 275VAC,
50 - 60Hz nominal (± 10%)
Different supply voltages available.
Measurement Input Range:
Voltage: 10 - 300 V AC (L-N)
20 - 520 V AC (L-L)
Current: 0.2 - 5.5 A AC
Frequency: 30 - 100 Hz
Accuracy:
Voltage: 0.5%+1digit
Current: 0.5%+1 digit
Frequency: 0.5%+1 digit
Power(kW,kVAr): 1.0%+2digit
Power factor: 2.0%+2digit
Measurement Range:
CT range: 5/5A to 5000/5A
VT range: 1.0/1 to 5000.0/1
kW range: 1.0 kW to 50.0 MW
Power Consumption: < 4 VA
Voltage burden: < 0.1VA per phase
Current burden: < 1VA per phase
Relay Outputs: 5A @ 250V AC
Digital Inputs:
Active level: 5 to 30V-DC or AC
Min pulse: 250ms.
Isolation: 1000V AC, 1 minute
Serial Port:
Signal level: RS-485
Protocol: Modbus RTU
Data Rate: 9600 bauds
Isolation: 500V AC, 1 minute
Operating Temperature: -20°C to +70°C (-4°F to +158°F).
Maximum humidity: 95% non-condensing.
Degree of Protection: IP 54 (Front Panel), IP 30 (Back panel)
Enclosure: Non-flammable, ROHS compliant
Installation: Flush mounting with rear brackets
Dimensions: 102x102x53mm (WxHxD)
Panel Cutout: 92x92mm
Weight: 350 gr
EU Directives:
2006/95/EC (LVD)
2004/108/EC (EMC)
Norms of reference:
EN 61010 (safety)
EN 61326 (EMC)